1. The magnetic material is not allowed to be close to the body of the magnetic flap level gauge, and the wire is fixed. Otherwise, it will affect the normal operation of the magnetic flap level gauge;
2. If the user uses the heat tracing pipe by himself, non-magnetic materials such as copper pipes must be used. The heat tracing temperature is determined according to the medium condition;
3. The installation of the magnetic flap level gauge must be vertical. A ball valve should be installed between the magnetic flap level gauge and the container guide tube for easy inspection and cleaning;
4. The medium should not contain solid impurities or magnetic substances to avoid jamming the float;
5. Before use, the ball below the zero position should be set to red with the correct magnetic steel, and the other balls should be set to white;
6. Open the bottom flange and insert the magnetic float (note: the end of the heavy end with the magnetic end up, can not be flipped.);
7. When commissioning, first open the upper pilot valve, then slowly open the lower valve to allow the medium to smoothly enter the main conduit (the medium should avoid the rapid impact of the float during operation, causing the float to fluctuate, affecting the display accuracy), observe the magnetic red and white ball Whether the flipping is normal, then close the lower pilot valve, open the drain valve, and let the liquid level in the main conduit drop. According to this method, it is normal, and it can be put into operation (except for special liquids such as corrosive);
8. The main conduit should be cleaned from time to time to remove impurities according to the medium;
9. For liquid level gauges exceeding a certain length (common type > 3 m, anti-corrosion type > 2 m), it is necessary to increase the intermediate reinforcement flange or ear climbing as a fixed support to increase the strength and overcome its own weight;
10. The installation position of the magnetic flap level gauge should be avoided or away from the inlet and outlet of the material medium to avoid rapid changes in the local area of ​​the material fluid and affect the accuracy of the liquid level measurement;
11. When equipped with a remote transmission instrument (UB or UK), the following must be done:
a) The remote transmission instrument should be placed close to the main pipe of the liquid level gauge and fixed with stainless steel hoop (disabling iron);
b) The sensing surface on the remote transmission supporting instrument should face and close to the main conduit;
c) The zero position of the remote transmission supporting instrument shall be on the same horizontal line as the zero position indication of the liquid level gauge;
d) The connection between the remote transmission supporting instrument and the display instrument or the industrial computer is preferably laid by a protective tube alone or with a shielded two-core cable;
e) After the wiring box of the junction box is laid, the sealing is required to be good, so as to prevent the intrusion of rainwater and moisture, so that the remote transmission supporting instrument cannot work normally. The junction box should be covered in time after the repair or debugging is completed.